Simplex 4100ES-S1 Specifications Page 125

  • Download
  • Add to my manuals
  • Print
  • Page
    / 173
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 124
F-4
Compatible Detectors, IDNET
The following lists the detectors approved for use with IDNet and shows current
rating and numbers allowed per loop.
Device Type Operating
Current mA
Maximum
Number Allowed
Per Loop
Maximum
Number
Allowed Per
Line
4098-9714E
Analogue Photoelectric
Smoke Detector
0.5
(2 with LED
on)
250 40*
4098-9717E
Analogue Ionisation
Smoke Detector
0.5
(2 with LED
on)
250 40*
4098-9733E
Analogue Heat Type A &
B Detector
0.5
(2 with LED
on)
250 40*
4098-9754E
Analogue Multi
(Heat/Photo)
Detector
0.5
(2 with LED
on)
250 40*
* Maximum allowed by AS 1670.1.
The 9714E, 9717E and 9733E detectors use a (4098-) 9789E addressable base
or 9794E addressable sounder base, or 9793 addressable isolator base. The
9754E uses a 9796E addressable base or 9795E sounder base.
The maximum specified loop/line resistance is 40.
The maximum number of LEDs switched on during Alarm on an IDNet loop is 20.