4100/4120
Programming
The DACT must be selected in the Programmer. Refer to Serial DACT Installation and Program-
ming Instructions (574-090) for specific programming requirements.
4100U/4100ES
Programming
The correct DACT card must be selected in the 4100U/ES Panel Programmer. Refer to the
ES Panel Programmers Manual (574-849).
Additional
Programming
When a DACT connects to a TL300, additional programming is required.
1. To monitor the relay contact of a relay located in the cabinet with the TL300. This relay will
energize and open the IDC circuit when the Ethernet connection to the Central station has been
broken.
2. Program a Relay so that it will energize on the telephone Line 1 or Line 2 fault. The N.O.
contacts will connect to GND and AN4 of the TL300.
An example equation is below. The Serial DACT is at address 9 and the Aux relay on the SPS
(Aux 3) is used.
INPUTS]
STATUS TBL
9-0-3 | CARDSTAT | CSP | PHONE LINE 1
OR STATUS TBL
9-0-4 | CARDSTAT | CSP | PHONE LINE 2
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
AUX3 | RELAY | RELAY | AUX RELAY CARD 1 RELAY CKT AUX3
[END OUTPUTS]
TL300
Programming
Refer to T-Link TL250/TL300 Network Internet Alarm Communicator #29034631 for informa-
tion concerning the programming of the TL300.
In addition to the required programming in the manual for the ULC compliance:
Section 035 PGM1 needs to be Enabled.
Section 039 needs to be code 98 24 hr. Panel Absent.