SP1 Fire Indicator Panel Operator’s Manual 4100ES-S1 Fire Indicator Panel Panel Operator’s Manual LT0395 Iss 1.2 Operator’s Man
x
1-1 This chapter provides an overview of the 4100ES-S1 operator interface and describes the normal appearance of the operator interface. Refer to
1-2 The 4100ES-S1 is supplied with an operator interface plus one expansion bay in a 21U sized cabinet. See Figure 1-1. The Zone Isolate modules
1-3 The Simplex 4100ES-S1 Fire Indicator Panel (FIP) has three general functions. It monitors fire alarm initiating points (smoke detectors, h
1-4 Table 1-1. Components of the Operator Interface (continued) LED/Key Description Refer To SYSTEM WARNINGS The System Warning LEDs – Isolat
1-5 Table 1-1. Components of the Operator Interface (continued) LED/Key Description Refer To Alphanumeric Display Displays text describing abno
1-6 The control keys and indicator LEDs are located on the far left of the operator interface as shown in Figure 1-3. Each control key is pressed
1-7 The 4100ES-S1 operator interface panel shows the following under normal conditions: Green AC Power LED is ON – indicating the panel is rec
2-1 An alarm condition occurs when an actuating device (such as a manual call point, smoke detector, etc.) activates. The 4100ES-S1 indicates the
2-2 When the first alarm condition is detected by the 4100ES-S1, the panel does the following to indicate the presence of the alarm: Red Fire A
2-3 Use the following procedure to acknowledge alarm(s): 1. Unlock and open the enclosure door. Read the alphanumeric display. It alternates b
2-4 When an alarm condition occurs, the building’s warning system activates to warn the building’s occupants about the alarm condition. In additio
2-5 Isolating ACF Outputs The Ancillary Control Facility (ACF) consists of relay outputs which can be used to control equipment which is not part o
2-6 The Ancillary Control Facility (see previous section) is used to control building air conditioning systems during a fire alarm. During the man
2-7 1. Select the point by repeatedly pressing the <ALARM ACK> key (for a point in alarm), <FAULT ACK> (for a point in fault), or &
2-8 The Alarm state and some Fault conditions latch within the panel so they can be acknowledged and viewed. When the latched states are no longer
3-1 Fault conditions are used to indicate something wrong, e.g. the presence of a field wiring problem (circuit break, short or ground), somewher
3-2 When a fault or isolate condition is detected by the 4100ES-S1, the operator interface does the following: The yellow ―FAULT‖ or ―ISOLATE‖ i
3-3 1. Unlock and open the panel door. The yellow Fault indicator (LED) will be flashing and the sounder (buzzer) sounding. The alphanumeric dis
4100ES-S1 Fire Indicator Panel Operator’s Guide Fire detectors in the building are grouped into zones (searchable areas). Zones can be Isolated by pre
3-4 You can view the list of acknowledged fault or isolate conditions at any time by using the following procedure. 1. Press the <FAULT ACK&
4-1 This chapter describes using the panel’s action keys (ALARM TEST, On, Off, etc.) to test and control system zones and points. Refer to the pa
4-2 Alarm Test forces a zone into the alarm state. Once the zone is in alarm, you can check to see if the system reacts in the way that it has bee
4-3 This section describes isolating and de-isolating zones. Isolating a zone does not prevent any of the points within the zone from going into t
4-4 Situations such as a malfunctioning detector causing false alarms, or an activated detector that prevents the system from being reset, can be
4-5 It may be necessary during maintenance of the system to turn the outputs (for example notification devices and relays) on or off. Turning an
5-1 Many of the operations that can be accomplished from the operator interface first require you to select the point on which you want to perform
5-2 Every system point is part of the ―Select a List of Points‖ list in the main menu. All points can be displayed sequentially by address order u
5-3 The Function/Numeric Keypad, shown in Figure 5-1 below, allows you to quickly select points. For example, pressing the ZONE key (key also labe
iv Australian Standard AS 4428.1, Control and Indicating Equipment. ActivFire Listing No. afp1682 The 4100ES-S1 is manufactured for : Tyco Fire
5-4 Table 5-1. Function/Numeric Keypad Press this Key on Keypad Data to Enter ZONE – allows you to select a Monitor Zone point. <ZONE> fol
6-1 This chapter describes displaying and modifying the attributes of a point. Refer to the page number listed in this table for information on a
6-2 Points can be selected in one of three ways: through the alarm, fault, or isolate list, using the MENU keys, or with the Function/Numeric keypa
6-3 Category Attribute Description TrueAlarm Sensors Only (smoke, heat, VESDA or 4-20mA) Present sensitivity selected Displays the current sen
6-4 This section describes using the <MORE INFO> key to modify the attributes of a point. Points can be selected in one of three ways — thr
6-5 Table 6-2. More Info Modifiable Attributes (continued) Attribute Description TrueAlarm Peak Analog Values Allows you to clear the peak value
7-1 This chapter describes setting the time and date on the system, logging in and out, and setting access levels for use by system operators. Re
7-2 Operator access levels 1 through 4 are available to support the system. Level 1 is the lowest operator access level and does not require a pas
7-3 The 4100ES-S1 uses four access levels, referred to by the numbers 1 through 4, to control what operators can do with the system. The system ty
v 4100ES-S1 Panel Supplied by: Installation Location Contract/Job Number As installed, FIP System Drawing Number Panel Installation Date Pan
7-4 If the passcode entered in Step 5 is correct, the following message is shown. After a brief pause, the system displays the granted acces
7-5 3. Press the <2> key. After a brief pause, the display shows a message similar to the one below. 4. Press the <C/EXIT>
8-1 When an abnormal condition occurs, a record of the event is placed in one of two logs generated by the system, depending on the nature of the
8-2 The Historical Alarm and Fault Logs can be viewed from the 4100ES-S1 operator interface. 1. Press the <MENU> key. 2. Using the <NE
9-1 This chapter describes service-related status and control procedures. Refer to the page number listed in this table for information on a spec
9-2 Follow these steps to set the time and date on the panel. 1. Press the <MENU> key. Press the <NEXT> or <PREVIOUS> key until
9-3 Follow these steps to display software revision information. 1. Press the MENU key. 2. Press the <NEXT> or <PREVIOUS> keys unt
9-4 Every card, including the Master Controller and all option cards, has a series of Card Status Points associated with it. For the SPS (System P
9-5 Network systems consist of multiple panels linked via a 4120 network. Each panel includes a programmer-defined node number, used to identify t
vi Approvals ... iv Manufacturer ..
9-6 The ―LAMP TEST‖ push-button on the operator interface is used to determine local lamp (LED) failures within the system. LEDs on the 4100ES-S1
9-7 The IDNet options allow the use of addressable devices and TrueAlarm sensors with the 4100ES-S1 FIP. Addressable devices communicate the exact
9-8 Press the <MORE INFO> key to obtain the next display: Device Address: 3-1 IDNet Device: M1-1 Press the <NEXT> key to obtain the
9-9 To view the average value of samples received from the sensor press the <NEXT> key again. Level 3 – Room 74 Average Value = 75 / Alarm
10-1 The following test features can be used when commissioning after the system is installed, and during periodic testing as required by code.
10-2 Walk Test™ is a software-based function and is programmed to meet the customer requirements. The system will pulse the signals for alarm condi
10-3 NOTE: Zero Code = 2 short pulses. Zone coding may be disabled for each of the eight Walk Test™ groups, Group 0 through Group 7, using
10-4 <3> Key - Allows you to choose between Zone Coding and Zero Coding. In Zone Coding a PNIS code for the tested zone is played (e.g.,
10-5 The Walk Test™ function has the following features: Abort Audible and Delay on Reactivation Active/Not Active Auto Abort on Alarm
vii Chapter 4 Testing and Controlling Points ...4-1 Introduction ...
10-6 The programmer has the ability to set a Reset Time Delay. The delay time period starts after a zone alarm is detected and runs until the dete
10-7 When a zone fault is detected, the Walk Test™ signals sound continuously for four seconds. The <3> key is used to enable/disable Zone C
10-8 Once the passcode has been entered, you may enter the Walk Test™ mode by performing the following procedures. 1. Press the <MENU> key.
10-9 5. Press the <1> key to enable/disable the Walk Test™ mode. The SYSTEM FAULT LED illuminates, the tone-alert sounds, and the LCD disp
10-10 The <OFF> key press will turn a control point off and prevent the automatic override, thus causing it to remain OFF. This action will
10-11 To turn a point ON, perform the following procedures. 1. Ensure the point to be turned ON is shown on the alphanumeric display. A typical
10-12 2. Press the <AUTO> key. A typical display is shown below. Press <ENTER> for AUTOmatic control SIGNAL CIRCUIT: SIG2 3. Pre
10-13 3. Press the <ENTER> key. The alphanumeric display shows the following message. Please stand by . . . ZONE 12 will ENABLE in 60 s
11-1 This chapter describes printer options and how to print a report. Refer to the page number listed in this table for information on a speci
viii Chapter 9 Service-Related Operations ...9-1 Introduction ...
11-2 The 4100ES-S1 includes two printer options: Select Report Printer and Terminate Current Report. Follow these steps to set these options. 1.
11-3 The system can generate any of the following reports. Report Description Alarm History Log Report Report includes all information contained i
12-1 It is a requirement of AS 1851 - Maintenance of Fire Protection Systems and Equipment, that tests be carried out to ensure the system is ful
12-2 Monthly Tests AS 1851 Item No. Description Action Required and Pass/Fail Criteria Test Facility, Procedure, Notes 2.1 Fire Alarm Simulate an a
12-3 Additional Tests to be Done Annually. AS 1851 Item No. Description Action Required and Pass/Fail Criteria Test Facility, Procedure, Notes 2.13
12-4 The 4100ES-S1 Fire Alarm Panel has no provision for load discharge testing of the battery at the levels required for yearly testing to AS 1851
ix Chapter 11 Printing Reports ............... 11-1 Introduction ...........
Comments to this Manuals