4100ES-S1 Programming Guide Document: LT0400
Appendices
12-4
12.2.2 Analog Points
Analog Points can have a value 0-65535 and can be used for Timers, Counters or store a
numerical value.
A0 – Number of Devices in Alarm
A1 – Number of Isolates
A2 – Number of Faults
A34 – System Startup pulse
A257 – Alarm and Fault Test Timeout
12.2.3 Lists
Lists are container objects used to group several points. A list inherits the states and status
of the points within the list and the list is used the same as a point.
L256 – Brigade call Alarm List
L257 – General Fire Trip List (ACF Isolatable)
L258 – Zone Alarm Test List
L259 – Zone Fault Test List
L260 – Zone Isolate Toggles
12.2.4 Physical Hardware Points (LEDs Relays etc)
Alarm Test Active LED or keyboard panel (P514)
A/C Trip LED (P521)
ACF Isolated LED (P517)
Bells Isolated LED (P518)
0-5-10 Warning System Isolated LED (P519)
0-5-11 Common Alarm LED
0-5-13 Fault Test Active LED (P515)
0-5-1 Alarm Fault Normal Button (P513)
0-5-2 A/C Reset Button (P522)
0-5-3 ACF Isolate Button (P517)
0-5-4 Bell Isolate Button (P518)
0-5-5 Warning System Isolate Button (P519)
0-7-3 City Alarm Relay
0-7-4 City Alarm Trouble Relay (FAULTS)
1-9 City Fire Relay 1 (ALARMS)
1-11 City Supervisory Relay 2 (ISOLATES)
1-12 City Trouble Relay 3 (FAULTS)
SIG3 ACF General Fire Trip (SPS NAC 1)
SIG4 Fire Alarm Bell (SPS NAC 2)
SIG5 Warning System (SPS NAC 3)