The followiong table shows the points abailable for mapping in the
Simplex 4100U IDnet Devices.
Simplex 4100U
IDnet Devices
Table 13: Simplex 4100U IDnet Devices
NPT NPA Units Description
BI 1-250 All of the following BI points support the trouble status:
State of net point (NPA)* 0-nor/open, 1-alarm/closed
AI**** 1-250 % or
DegF
Current % of alarm if True Alarm smoke device*** or
Current Temperature if True Alarm heat device.
ADI 1-250 Use for WSC and TPHOTO and SPHOTO for the following
ADI points:
0-normal/open, 1-Fire Alarm, 2-Priority 2 Alarm,
4-Supervisory, 8-Utility Monitor/Analog Pseudo State,
16-Control State is Closed**
Note: If a point is in more than one state, a combination of
the above codes will be output. For example, if the
point is in closed and supervisory, the value = 20.
* A closed state indicates that the point is in one of the following states:
Fire Alarm Abnormal State
Priority 2 Abnormal State
Supervisory Abnormal State
Utility Monitor, Digital/Analog Pseudo State Closed
Control State Closed (only applicabe if sim_idnt.vct is used)
** Use the sim_mapa.vct or sm_mapa.vct file to ignore the control state.
*** Points which are not mapped to True Alarm or heat devices will be unreliable.
**** Metasys Integrator system supports reading analog values for the 4100U. These
are read on a very slow poll and should not be used for fire alarm reporting but can
provide warning alarms for preventative maintance.
Metasys Integrator Simplex Application Application Note 23