Metasys Integrator Simplex Application Application Note 3
Introduction
This document explains Metasys Integrator Simplex
4100/4100U/4120/4020 Computer Port applications. Use this document
with the Metasys Integrator unit technical bulletins, which provide
information on installing and commissioning the Metasys Integrator unit.
For information on Simplex equipment, see Simplex documentation
(obtainable from a Simplex representative).
Note: If you use a Universal Packaging Module (UPM) enclosure, you
must install the Metasys Integrator unit 300 Series in a two high
enclosure (EN-EWC25-0) rather than a one high enclosure
(EN-EWC13-0) as shown in the figures in this application note.
The Metasys Integrator unit is not Underwriters Laboratories Inc. (UL)
Listed as a fire alarm control unit (UOJZ). However, the
Metasys Integrator unit is UL Listed as a smoke control accessory unit
(UUKL) for smoke control applications. The Metasys Integrator unit is
designed to provide secondary monitoring for a fire alarm, while the
Simplex fire alarm control panels provide notification and control
functions.
IMPORTANT: Do not use the Metasys Integrator unit as a primary
fire alarm control unit. The Metasys Integrator unit
provides secondary monitoring and can be used for
smoke control applications. A fire alarm control panel
is necessary to provide notification and alarm control
functions. Use of the Metasys Integrator unit alone
may result in a failure to obtain proper response to a
fire with a resulting greater risk of property damage,
personal injuries, or deaths.
The Metasys Integrator unit can connect to either a network of
Simplex panels via a Simplex Network Display Unit (NDU), or to an
individual panel. They cannot be combined on the same
Metasys Integrator panel.
Application
Details
Each Metasys Integrator vendor port can connect to one 4100/4100U/4120
or 4020 Computer Port.
Both the 4100U and NDU can support more data than one NCM can
support. To ensure resonable performance, do not define more than
2,500 objects per NCM. Companion systems do not support more than
800 points.