Metasys Network Setup
Metasys network setup is described in the Metasys Integrator unit
technical bulletins. This section contains details specific to Simplex
applications.
We recommend that all points that report an alarm or trouble status be
directly mapped to BI objects.
Mapping to a
CS Object
Table 17: Software Model and CS Object Definition
Application Software Model
(on Tables and
Models CD-ROM)
Display Attribute
(recommended)
NT Command
Attribute
(recommended)
4100/4100U/4120 Master
Controller
SIM_MAST.DDL
BI5
Master Sonalert
BI5
Master Sonalert
Digital Pseudo Card SIM_DIGP.DDL BI1 BI1
Network Interface Card SIM_NETC.DDL BI1
State of Point 1
BI1
State of Point 1
Network Interface Card
Slot
SIM_NETS.DDL BI1
State of Point 1
BI1
State of Point 1
Four/Eight Point
Auxiliary Relay Card and
Eight Point
Multi-function I/O Card
and Mapnet II Device
SIM_PNTC.DDL BI1 BI1
Auxiliary Relay Card and
Multi-function Card
Point Status
SIM_PNTS.DDL BI1 BI1
Mapnet Interface Card SIM_MAPC.DDL BI1
Card
Missing/Failed
BI1
Remote User Interface
Card
SIM_RUIC.DDL BI1
Card
Missing/Failed
BI1
Device Points Status SIM_MAPS.DLL BI1 BI1
IDNet Card Statuses SIM_IDNC.DLL BI1
Card
Missing/Failed
BI1
IDNet devices SIM_IDDS.DLL AI1
Current % of
Alarm or
Temperature
BI1
State of point 1
4100U Power Supplies
(SPS/XPS/RPS/XBC)
Card
SIM_SPS.DLL BI1
Card
Missing/Failed
BI1
4100U Transponder
Interface Card (TIC)
Card Status
SIM_TIC.DLL BI1
Card
Missing/Failed
BI1